This technical bulletin addresses abnormal system resets in ABB Totalflow G4 products caused by a voltage regulator issue on 32MB engine cards manufactured between March 2012 and January 2013. It details affected products, part numbers, and the resolution involving a hardware modification (replacing the voltage regulator) and software updates to prevent temperature-related voltage drops and system resets.