This technical bulletin corrects a wiring diagram error for the Q64AD module in the manual (BCN-P5781-A) supplied since August 2010, specifying that cables should connect to "V+", "V-", and "SLD" instead of "V-", "I+", and "SLD". Incorrect wiring will cause the module to be regarded as not-wired but will not result in failure.