MELSEC iQ-R AnyWireASLINK Modules Solderless Terminal Correction Notice
This technical bulletin corrects the model names of bar solderless terminals listed in the user's manuals for the MELSEC iQ-R AnyWireASLINK master module (RJ51AW12AL) and the CC-Link IE TSN—AnyWireASLINK bridge module (NZ2AW1GNAL). It specifies that the incorrect descriptions (AI 0,75-8 GY and AI 1,5-8 GY) should be replaced with the correct models (AI 0,75-10 GY and AI 1,5-10), noting sleeve length differences and warning that improper terminals may not fix securely to the terminal block.